Home » Appliances » Cummins Onan DGCA Specs (Power | Fuel Consumption)

Cummins Onan DGCA Specs (Power | Fuel Consumption)

The Cummins Onan DGCA generator is listed with standby output of 50 kW, diesel fuel, 60 Hz operation, 9 available voltage configurations, Three phase, and sound level of 68 dBA @ 23 ft (7 m).

Cummins Onan Generator Specifications

Generator • diesel • 60 Hz • Three phase

Standby power: 50 kWVoltage options: 9 configurationsDry weight: 1,720 lb (780 kg)

Key specifications

50 kW Standby power
diesel Fuel
9 configurations Voltage options
Three phase Phase
1,720 lb (780 kg) Dry weight
68 dBA @ 23 ft (7 m) Sound level
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Power-to-weight
Standby output per 1,000 lb of dry weight versus similar-output Cummins Onan models.
This model

29.1 kW

Peer average

20.4 kW

95th percentile
Power output
Low 45 kW High 50 kW
Standby

50 kW

Prime

45 kW

Model spec snapshot
Representative numeric specifications from this generator.
50 kWStandby
1,719.61 lbWeight
68 dBASound

How the Cummins Onan DGCA compares

This compares the supplied numeric specification with Cummins Onan generators in the same broad standby-power class where enough comparable data exists.

Standby power
50 kW
21% above avg
81st percentile
Dry weight
1,720 lb
21% below avg
22nd percentile
Sound level
68 dBA
6% below avg
30th percentile
Oil capacity
2.88 gal
13% above avg
50th percentile
Standby power50 kW
Low 30 kWAverage 41.2 kWHigh 55 kW

About 21% above the similar-output Cummins Onan average. Around the 81st percentile for this field.

Dry weight1,720 lb
Low 1,120 lbAverage 2,187 lbHigh 3,476 lb

About 21% below the similar-output Cummins Onan average. Around the 22nd percentile for this field.

Sound level68 dBA
Low 68 dBAAverage 72.7 dBAHigh 86.4 dBA

About 6% below the similar-output Cummins Onan average. Around the 30th percentile for this field.

Oil capacity2.88 gal
Low 1.14 galAverage 2.54 galHigh 4.06 gal

About 13% above the similar-output Cummins Onan average. Around the 50th percentile for this field.

This model Peer average

Generator information

Manufacturer Cummins Onan
Model DGCA
Generator type Generator
Fuel diesel
Frequency 60 Hz

Electrical output

Standby power 50 kW
Prime power 45 kW
Standby kVA 63.0
Voltage options 120/208 V, 127/220 V, 240/416 V, 277/480 V, 120/240 V, 139/240 V, 254/440 V, 220/380 V, 347/600 V
Phase Three phase
Power factor 0.8

Engine, cooling and controls

Engine model Cummins/Onan 4BT3.9
Engine displacement 238 cu in (3.9 L)
Engine coolant capacity 4.68 gal (17.7 L)
Oil capacity 2.88 gal (10.9 L)
Coolant capacity 6.87 gal (26 L)
Maximum ambient 104 °F (40 °C)
Controller Detector, PCC, PowerCommand 2100, PowerCommand 3100, PowerCommand PCC2100, Sentinel
Alternator Cummins/Onan 12-lead reconnectable alternator fitted with voltage selection switch
Emissions Tier 1

Physical specifications

Dry weight 1, 720 lb (780 kg)
Dimensions (L × W × H) 82.8 × 40 × 47.5 in (2104 × 1016 × 1207 mm)
Sound level 68 dBA @ 23 ft (7 m)

Battery

Battery group 4
Battery cranking 1080 CCA
Battery voltage 12 V
Battery quantity 1

Fuel system and runtime

Fuel tank 6.34 gal (24 L)
Tank runtime 15.9 hr

Maintenance and service parts

Engine oil Interval: 500 hr; Specification: API Class CC/CD with a maximum sulphated ash content of 1.85 percent; Capacity: 17.3 quarts
Oil filter Interval: 500 hr; Specification: Spin-off throw-away units, filled with diesel fuel and put a light coat of fuel on the sealing gasket
Fuel filter Interval: 100 hr; Specification: Spin-off throw-away units, filled with diesel fuel and put a light coat of fuel on the sealing gasket
Air filter Interval: 8760 hr; Specification: Replace yearly or sooner if the service indicator button pops up indicating air restriction
Coolant Capacity: 21.0 litres

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Cummins North America generator website.