The Cummins Onan DQLH generator is listed with standby output of 2750 kW, Ultra-low sulphur diesel (15 ppm sulphur) fuel, 60 Hz operation, and Three phase.
Generator • Ultra-low sulphur diesel (15 ppm sulphur) • 60 Hz • Three phase
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
54.6 kW
55.6 kW
2,750 kW
2,500 kW
How the Cummins Onan DQLH compares
This compares the supplied numeric specification with Cummins Onan generators in the same broad standby-power class where enough comparable data exists.
About 50% above the similar-output Cummins Onan average. Around the 89th percentile for this field.
About 67% above the similar-output Cummins Onan average. Around the 83rd percentile for this field.
About 110% above the similar-output Cummins Onan average. Around the 99th percentile for this field.
Generator information
| Manufacturer | Cummins Onan |
|---|---|
| Model | DQLH |
| Generator type | Generator |
| Fuel | Ultra-low sulphur diesel (15 ppm sulphur) |
| Frequency | 60 Hz |
Electrical output
| Standby power | 2750 kW |
|---|---|
| Prime power | 2500 kW |
| Standby kVA | 3438.0 |
| Phase | Three phase |
Engine, cooling and controls
| Engine model | Cummins/Onan QSK78-G14 |
|---|---|
| Aspiration / cooling | Turbocharged and low temperature after-cooled |
| Rated engine speed | 1800 rpm |
| Engine oil capacity | 109.1 gal (413 L) |
| Oil capacity | 109.1 gal (413 L) |
| Coolant capacity | 195 gal (738 L) |
| Maximum ambient | 109 °F (43 °C) |
| Controller | PowerCommand 3.3 |
| Emissions | EPA Stationary non-Emergency Tier 4 |
Physical specifications
| Dry weight | 50, 409 lb (22, 865 kg) |
|---|
Battery
| Battery voltage | 24VDC V |
|---|
Fuel consumption
| Standby | 63.3 gal/h (239.0 L/h) @ 0%; 103.4 gal/h (391.0 L/h) @ 1%; 143.4 gal/h (542.0 L/h); 183.4 gal/h (694.0 L/h) |
|---|---|
| Prime | 59.7 gal/h (226.0 L/h) @ 0%; 96.1 gal/h (364.0 L/h) @ 1%; 132.5 gal/h (501.0 L/h); 169.0 gal/h (639.0 L/h) |
Maintenance and service parts
| Fuel filter | Specification: Triple element, 10 micron filtration, spin-on fuel filter with water separator |
|---|---|
| Air filter | Specification: Dry replaceable element standard; heavy duty optional |
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Cummins North America generator website.