The Generac MG200 compressor is listed with standby output of 200 kW, Natural Gas fuel, 60 Hz operation, 120/208 V, 277/480 V, 346/600 V output, Three phase, and sound level of 83.5 dBA @ 23 ft (7 m).
Generator • Natural Gas • 60 Hz • Three phase
Key specifications
Visual model specs
Built only from this model’s supplied generator specifications.
200 kW
180 kW
9.06 gal
10.01 gal
How the Generac MG200 compares
This compares the supplied numeric specification with Generac generators in the same broad standby-power class where enough comparable data exists.
About 22% below the similar-output Generac average. Around the 32nd percentile for this field.
About 16% below the similar-output Generac average. Around the 34th percentile for this field.
About 3% above the similar-output Generac average. Around the 54th percentile for this field.
About 21% above the similar-output Generac average. Around the 82nd percentile for this field.
Generator information
| Manufacturer | Generac |
|---|---|
| Model | MG200 |
| Generator type | Generator |
| Fuel | Natural Gas |
| Frequency | 60 Hz |
Electrical output
| Standby power | 200 kW |
|---|---|
| Prime power | 180 kW |
| Standby kVA | 250.0 |
| Voltage options | 120/208 V, 277/480 V, 346/600 V |
| Phase | Three phase |
| Power factor | 0.8 |
| Circuit breaker | 1000 A |
Engine, cooling and controls
| Oil capacity | 9.06 gal (34.3 L) |
|---|---|
| Coolant capacity | 10 gal (37.9 L) |
| Maximum ambient | 122 °F (50 °C) |
| Controller | Digital G-200, G-200, Power Zone Pro Sync, PowerManager Digital Platform, PowerManager Digital Platform (PM-DCP) |
| Alternator | 520 (4-pole, Class H insulation) |
| Emissions | EPA Certified Stationary Emergency |
Physical specifications
| Dry weight | 5, 754 lb (2, 610 kg) |
|---|---|
| Dimensions (L × W × H) | 128 × 52.9 × 67.4 in (3250 × 1344 × 1711 mm) |
| Sound level | 83.5 dBA @ 23 ft (7 m) |
Battery
| Battery group | 4D |
|---|---|
| Battery cranking | 925 CCA |
| Battery voltage | 12 VDC V |
| Battery quantity | 2 |
Disclaimer: Specifications should be verified against the official owner’s manual and confirmed on the Generac USA website.