Home » Appliances » Kohler 1000REOZMD Specs (Power | Consumption)

Kohler 1000REOZMD Specs (Power | Consumption)

The Kohler 1000REOZMD generator is listed with standby output of 1010 kW, Diesel fuel, 60 Hz operation, 4 available voltage configurations, and Three phase.

Kohler Generator Specifications

Generator • Diesel • 60 Hz • Three phase

Standby power: 1010 kWVoltage options: 4 configurations

Key specifications

1010 kW Standby power
Diesel Fuel
4 configurations Voltage options
Three phase Phase
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Fuel consumption by load
How fuel use changes as generator load increases.
25% load

21.5 gal/hr

50% load

39.8 gal/hr

75% load

59.7 gal/hr

100% load

75 gal/hr

Power output
Low 920 kW High 1,010 kW
Standby

1,010 kW

Prime

920 kW

How the Kohler 1000REOZMD compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
1,010 kW
48% below avg
7th percentile
Oil capacity
52.83 gal
19% below avg
39th percentile
Standby power1,010 kW
Low 1,000 kWAverage 1,949.6 kWHigh 3,480 kW

About 48% below the similar-output Kohler average. Around the 7th percentile for this field.

Oil capacity52.83 gal
Low 25.87 galAverage 65.49 galHigh 110.95 gal

About 19% below the similar-output Kohler average. Around the 39th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model 1000REOZMD
Generator type Generator
Fuel Diesel
Frequency 60 Hz

Electrical output

Standby power 1010 kW
Prime power 920 kW
Standby kVA 1263.0
Voltage options 240/416 V, 277/480 V, 220/380 V, 347/600 V
Phase Three phase
Power factor 0.8

Engine, cooling and controls

Engine model Mitsubishi S12H-Y2PTAW-1
Engine displacement 2, 265 cu in (37.11 L)
Aspiration / cooling Turbocharged
Rated engine speed 1800 rpm
Engine oil capacity 52.8 gal (200 L)
Engine coolant capacity 76.1 gal (288 L)
Oil capacity 52.8 gal (200 L)
Coolant capacity 76.1 gal (288 L)
Maximum ambient 104 °F (40 °C)
Alternator 5M4044
Emissions Tier 2 EPA-Certified for Stationary Emergency Applications

Physical specifications

Dimensions (L × W × H) 201 × 76 × 101.2 in (5106 × 1931 × 2571 mm)

Battery

Battery cranking 1150 CCA
Battery voltage 12 V
Battery quantity 2

Fuel consumption

Standby 21.5 gal/h (81.0 L/h) @ 25%; 39.8 gal/h (151.0 L/h) @ 50%; 59.7 gal/h (226.0 L/h) @ 75%; 75.0 gal/h (284.0 L/h) @ 100%
Prime 20.2 gal/h (76.0 L/h) @ 25%; 36.0 gal/h (136.0 L/h) @ 50%; 54.6 gal/h (207.0 L/h) @ 75%; 70.2 gal/h (266.0 L/h) @ 100%

Maintenance and service parts

Engine oil Interval: 30 hr; Capacity: 200.0
Oil filter Part number: GM13942; Specification: Cartridge; Capacity: ×5
Fuel filter Capacity: ×4
Coolant Specification: Demineralized water or distilled water, 40-60% anti-freeze based on a theoretical temperature that is 9-18°F (5-10°C) below the lowest temperature expected in the area

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.