The Kohler 120REOZT4 generator is listed with standby output of 105 kW, Diesel fuel, 60 Hz operation, 115 V, 200 V output, Single phase / Three, and sound level of 71 dBA @ 23 ft (7 m).
Generator • Diesel • 60 Hz • Single phase / Three
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
0.8 gal/hr
2.7 gal/hr
4.3 gal/hr
6 gal/hr
8.1 gal/hr
240.1 hr
71.1 hr
44.7 hr
32 hr
23.7 hr
17.9 kW
29.1 kW
105 kW
96 kW
How the Kohler 120REOZT4 compares
This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.
About 17% above the similar-output Kohler average. Around the 77th percentile for this field.
About 56% above the similar-output Kohler average. Around the 84th percentile for this field.
Very close to the similar-output Kohler average. Around the 75th percentile for this field.
About 61% above the similar-output Kohler average. Around the 93rd percentile for this field.
Generator information
| Manufacturer | Kohler |
|---|---|
| Model | 120REOZT4 |
| Generator type | Generator |
| Fuel | Diesel |
| Frequency | 60 Hz |
Electrical output
| Standby power | 105 kW |
|---|---|
| Prime power | 96 kW |
| Standby kVA | 131.0 |
| Voltage options | 115 V, 200 V |
| Phase | Single phase / Three |
| Circuit breaker | 400 A |
Engine, cooling and controls
| Engine model | John Deere 4.5 L |
|---|---|
| Engine displacement | 275 cu in (4.5 L) |
| Oil capacity | 5.55 gal (21 L) |
| Coolant capacity | 6.89 gal (26.1 L) |
| Maximum ambient | 113 °F (45 °C) |
| Controller | Decision-Maker 3500 |
| Alternator | Kohler 4R12X |
| Emissions | Tier 4 Final |
Physical specifications
| Dry weight | 5, 864 lb (2, 660 kg) |
|---|---|
| Dimensions (L × W × H) | 116.2 × 44.1 × 84.9 in (2951 × 1119 × 2156 mm) |
| Sound level | 71 dBA @ 23 ft (7 m) |
Battery
| Battery cranking | 450 CCA |
|---|---|
| Battery voltage | 12 V |
| Battery quantity | 1 |
Fuel system and runtime
| Fuel tank | 192.1 gal (727 L) |
|---|---|
| Tank runtime | 24 hr |
Fuel consumption
| Standby | 0.8 gal/h (3.2 L/h) @ 25%; 2.7 gal/h (10.4 L/h) @ 50%; 4.3 gal/h (16.3 L/h) @ 75%; 6.0 gal/h (22.9 L/h) @ 100%; 8.1 gal/h (30.8 L/h) |
|---|---|
| Prime | 0.8 gal/h (3.2 L/h) @ 25%; 2.6 gal/h (9.8 L/h) @ 50%; 4.9 gal/h (18.5 L/h) @ 75%; 6.2 gal/h (23.5 L/h) @ 100%; 7.4 gal/h (28.0 L/h) |
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.