The Kohler 125REOZT generator is listed with standby output of 128 kW, Diesel fuel, and 60 Hz operation.

Kohler Generator Specifications

Generator • Diesel • 60 Hz

Standby power: 128 kW

Key specifications

128 kW Standby power
Diesel Fuel
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Fuel consumption by load
How fuel use changes as generator load increases.
50% load

5.7 gal/hr

75% load

7.8 gal/hr

100% load

8.9 gal/hr

Power output
Low 116 kW High 128 kW
Standby

128 kW

Prime

116 kW

How the Kohler 125REOZT compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
128 kW
42% above avg
98th percentile
Oil capacity
8.72 gal
152% above avg
99th percentile
Standby power128 kW
Low 60 kWAverage 90 kWHigh 127 kW

About 42% above the similar-output Kohler average. Around the 98th percentile for this field.

Oil capacity8.72 gal
Low 1.24 galAverage 3.45 galHigh 7.29 gal

About 152% above the similar-output Kohler average. Around the 99th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model 125REOZT
Generator type Generator
Fuel Diesel
Frequency 60 Hz

Electrical output

Standby power 128 kW
Prime power 116 kW
Standby kVA 160.0

Engine, cooling and controls

Engine model John Deere 6068HFS82
Engine displacement 415 cu in (6.8 L)
Aspiration / cooling Turbocharged
Rated engine speed 1800 rpm
Engine oil capacity 8.72 gal (33 L)
Engine coolant capacity 6.82 gal (25.8 L)
Oil capacity 8.72 gal (33 L)
Controller Decision-Maker 1000
Alternator Leroy-Somer LSA442S7

Fuel consumption

Prime 5.7 gal/h (21.76 L/h) @ 50%; 7.8 gal/h (29.41 L/h) @ 75%; 8.9 gal/h (33.74 L/h) @ 100%

Maintenance and service parts

Engine oil Interval: 500 hr
Air filter Specification: clean when clogging indicator is red, replace after 6 cleanings or once a year
Coolant Specification: drain and flush every 2500 hours/3 years with John Deere COOL GARD, otherwise every 2000 hours/2 years
Belt Specification: check tension every 500 hours on 3029 and 4039 engines, and on 4045 and 6068 engines with manual tensioner. Check automatic tensioner every 1000 hours/once a year on 4045 and 6068 engines.

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.