The Kohler 12RESV generator is listed with standby output of 12 kW, Natural Gas fuel, 60 Hz operation, 120 V, 240 V output, Single phase, rated current of 50 A, and sound level of 67 dBA @ 23 ft (7 m).
Generator • Natural Gas • 60 Hz • Single phase
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
27.8 kW
24.8 kW
How the Kohler 12RESV compares
This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.
About 55% above the similar-output Kohler average. Around the 87th percentile for this field.
About 24% above the similar-output Kohler average. Around the 70th percentile for this field.
About 22% above the similar-output Kohler average. Around the 74th percentile for this field.
About 3% below the similar-output Kohler average. Around the 59th percentile for this field.
About 38% below the similar-output Kohler average. Around the 30th percentile for this field.
Generator information
| Manufacturer | Kohler |
|---|---|
| Model | 12RESV |
| Generator type | Generator |
| Fuel | Natural Gas |
| Frequency | 60 Hz |
Electrical output
| Standby power | 12 kW |
|---|---|
| Standby kVA | 12.0 |
| Voltage options | 120 V, 240 V |
| Phase | Single phase |
| Rated current | 50 A |
| Power factor | 1.0 |
| Circuit breaker | 60 A |
Engine, cooling and controls
| Engine model | Kohler KT725 |
|---|---|
| Engine displacement | 44 cu in (0.725 L) |
| Aspiration / cooling | Air-Cooled |
| Rated engine speed | 3600 rpm |
| Engine oil capacity | 0.5 gal (1.9 L) |
| Oil capacity | 0.5 gal (1.9 L) |
| Controller | DC2, RDC2 |
| Alternator | Kohler 2F4 |
| Emissions | EPA 40 CFR 60 |
Physical specifications
| Dry weight | 432 lb (196 kg) |
|---|---|
| Dimensions (L × W × H) | 30.6 × 28 × 32.4 in (777 × 712 × 824 mm) |
| Sound level | 67 dBA @ 23 ft (7 m) |
Battery
| Battery group | 51 |
|---|---|
| Battery cranking | 500 CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
Fuel consumption
| Standby | 25%; 50%; 75%; 100% |
|---|---|
| Exercise | 2.1 L/h @ 100% |
Maintenance and service parts
| Engine oil | Interval: 100 hr; Specification: 5W-30 API Service Class SG, SH, or SJ synthetic oil; Capacity: 1.9 L |
|---|---|
| Oil filter | Interval: 100 hr |
| Air filter | Interval: 150 hr |
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.