The Kohler 1350REOZDB generator is listed with standby output of 1224 kW, Diesel fuel, and 50 Hz operation.
Generator • Diesel • 50 Hz
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
28.6 gal/hr
50 gal/hr
71.1 gal/hr
92.1 gal/hr
1,224 kW
1,112 kW
How the Kohler 1350REOZDB compares
This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.
About 37% below the similar-output Kohler average. Around the 17th percentile for this field.
About 5% above the similar-output Kohler average. Around the 62nd percentile for this field.
Generator information
| Manufacturer | Kohler |
|---|---|
| Model | 1350REOZDB |
| Generator type | Generator |
| Fuel | Diesel |
| Frequency | 50 Hz |
Electrical output
| Standby power | 1224 kW |
|---|---|
| Prime power | 1112 kW |
| Standby kVA | 1530.0 |
Engine, cooling and controls
| Engine model | MTU 12V4000 (T123-7M35) |
|---|---|
| Engine displacement | 2, 990 cu in (49 L) |
| Aspiration / cooling | Turbocharged, Intercooled |
| Rated engine speed | 1500 rpm |
| Engine oil capacity | 68.7 gal (260 L) |
| Engine coolant capacity | 155.1 gal (587 L) |
| Oil capacity | 68.7 gal (260 L) |
| Controller | Decision-Maker 550 |
| Alternator | 7M4050 |
Fuel consumption
| Standby | 28.6 gal/h (108.1 L/h) @ 25%; 50.0 gal/h (189.1 L/h) @ 50%; 71.1 gal/h (269.3 L/h) @ 75%; 92.1 gal/h (348.5 L/h) @ 100% |
|---|---|
| Prime | 25.9 gal/h (98.2 L/h) @ 25%; 43.9 gal/h (166.3 L/h) @ 50%; 62.2 gal/h (235.6 L/h) @ 75%; 80.5 gal/h (304.9 L/h) @ 100% |
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.