The Kohler 145REOZT4 generator is listed with standby output of 130 kW, Diesel fuel, 60 Hz operation, 115 V, 200 V output, Single phase / Three, and sound level of 70 dBA @ 23 ft (7 m).
Generator • Diesel • 60 Hz • Single phase / Three
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
0.8 gal/hr
3 gal/hr
5.1 gal/hr
7.2 gal/hr
9.4 gal/hr
345.1 hr
92 hr
54.1 hr
38.3 hr
29.4 hr
16.5 kW
29.1 kW
130 kW
117 kW
How the Kohler 145REOZT4 compares
This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.
About 44% above the similar-output Kohler average. Around the 99th percentile for this field.
About 110% above the similar-output Kohler average. Around the 91st percentile for this field.
Very close to the similar-output Kohler average. Around the 55th percentile for this field.
About 118% above the similar-output Kohler average. Around the 97th percentile for this field.
Generator information
| Manufacturer | Kohler |
|---|---|
| Model | 145REOZT4 |
| Generator type | Generator |
| Fuel | Diesel |
| Frequency | 60 Hz |
Electrical output
| Standby power | 130 kW |
|---|---|
| Prime power | 117 kW |
| Standby kVA | 163.0 |
| Voltage options | 115 V, 200 V |
| Phase | Single phase / Three |
Engine, cooling and controls
| Engine model | John Deere 6.8 L |
|---|---|
| Engine displacement | 415 cu in (6.8 L) |
| Oil capacity | 7.53 gal (28.5 L) |
| Coolant capacity | 9.4 gal (35.6 L) |
| Maximum ambient | 122 °F (50 °C) |
| Controller | Decision-Maker 3500 |
| Alternator | Kohler 4R13X |
| Emissions | Tier 4 Final |
Physical specifications
| Dry weight | 7, 899 lb (3, 583 kg) |
|---|---|
| Dimensions (L × W × H) | 150.9 × 46.9 × 90.3 in (3834 × 1190 × 2294 mm) |
| Sound level | 70 dBA @ 23 ft (7 m) |
Battery
| Battery cranking | 400 CCA |
|---|---|
| Battery voltage | 12 V |
| Battery quantity | 2 |
Fuel system and runtime
| Fuel tank | 276.1 gal (1, 045 L) |
|---|---|
| Tank runtime | 24 hr |
Fuel consumption
| Standby | 0.8 gal/h (3.0 L/h) @ 25%; 3.0 gal/h (11.3 L/h) @ 50%; 5.1 gal/h (19.3 L/h) @ 75%; 7.2 gal/h (27.2 L/h) @ 100%; 9.4 gal/h (34.0 L/h) |
|---|---|
| Prime | 0.8 gal/h (3.0 L/h) @ 25%; 2.8 gal/h (10.6 L/h) @ 50%; 4.9 gal/h (18.5 L/h) @ 75%; 6.2 gal/h (23.5 L/h) @ 100%; 8.6 gal/h (32.5 L/h) |
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.