Home » Appliances » Kohler 3250REOZD Specs (Power | Consumption)

Kohler 3250REOZD Specs (Power | Consumption)

The Kohler 3250REOZD generator is listed with standby output of 3250 kW, diesel fuel, 60 Hz operation, 6 available voltage configurations, and Three phase.

Kohler Generator Specifications

Generator • diesel • 60 Hz • Three phase

Standby power: 3250 kWVoltage options: 6 configurations

Key specifications

3250 kW Standby power
diesel Fuel
6 configurations Voltage options
Three phase Phase
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Fuel consumption by load
How fuel use changes as generator load increases.
25% load

67.2 gal/hr

50% load

118.1 gal/hr

75% load

170.6 gal/hr

100% load

224.2 gal/hr

Power output
Low 2,800 kW High 3,250 kW
Standby

3,250 kW

Prime

2,800 kW

How the Kohler 3250REOZD compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
3,250 kW
67% above avg
94th percentile
Oil capacity
103.03 gal
57% above avg
86th percentile
Standby power3,250 kW
Low 1,000 kWAverage 1,949.6 kWHigh 3,480 kW

About 67% above the similar-output Kohler average. Around the 94th percentile for this field.

Oil capacity103.03 gal
Low 25.87 galAverage 65.49 galHigh 110.95 gal

About 57% above the similar-output Kohler average. Around the 86th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model 3250REOZD
Generator type Generator
Fuel diesel
Frequency 60 Hz

Electrical output

Standby power 3250 kW
Prime power 2800 kW
Standby kVA 4063.0
Voltage options 277/480 V, 347/600 V, 2400/4160 V, 7200/1247 V, 7620/1320 V, 7970/1380 V
Phase Three phase
Power factor 0.8

Engine, cooling and controls

Engine model MTU 20V4000G83L
Engine displacement 5, 822 cu in (95.4 L)
Aspiration / cooling Turbocharged, Intercooled
Rated engine speed 1800 rpm
Engine oil capacity 103 gal (390 L)
Engine coolant capacity 216.1 gal (818 L)
Oil capacity 103 gal (390 L)
Coolant capacity 216.1 gal (818 L)
Maximum ambient 104 °F (40 °C)
Controller Decision-Maker 550, Decision-Maker 6000
Alternator 10M1110
Emissions Tier 2 EPA-Certified for Stationary Emergency Applications

Physical specifications

Dimensions (L × W × H) 318.4 × 120.6 × 129.6 in (8087 × 3062 × 3292 mm)

Battery

Battery cranking 1150 CCA
Battery voltage 12 V
Battery quantity 4

Fuel consumption

Standby 67.2 gal/h (254.4 L/h) @ 25%; 118.1 gal/h (447.1 L/h) @ 50%; 170.6 gal/h (645.9 L/h) @ 75%; 224.2 gal/h (848.8 L/h) @ 100%
Prime 58.7 gal/h (222.1 L/h) @ 25%; 108.0 gal/h (408.7 L/h) @ 50%; 147.2 gal/h (557.1 L/h) @ 75%; 188.7 gal/h (714.3 L/h) @ 100%

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.

Ernie Lo

Ernie Lo is a qualified web designer and web developer. He works as an IT support technician and website manager at Benleigh Vending, and he also fixes vending machines.

Recent Posts