The Kohler 600REOZV generator is listed with standby output of 600 kW, diesel fuel, 60 Hz operation, 6 available voltage configurations, Three phase, and rated current of 2082 / 1969 / 1805 / 1041 / 903 A.
Generator • diesel • 60 Hz • Three phase
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
11 gal/hr
20 gal/hr
29.7 gal/hr
40.8 gal/hr
55.7 kW
55.3 kW
600 kW
485 kW
How the Kohler 600REOZV compares
This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.
About 3% below the similar-output Kohler average. Around the 53rd percentile for this field.
About 13% below the similar-output Kohler average. Around the 46th percentile for this field.
About 39% below the similar-output Kohler average. Around the 47th percentile for this field.
Generator information
| Manufacturer | Kohler |
|---|---|
| Model | 600REOZV |
| Generator type | Generator |
| Fuel | diesel |
| Frequency | 60 Hz |
Electrical output
| Standby power | 600 kW |
|---|---|
| Prime power | 485 kW |
| Standby kVA | 750.0 |
| Voltage options | 120/208 V, 127/220 V, 139/240 V, 240/416 V, 277/480 V, 220/380 V |
| Phase | Three phase |
| Rated current | 2082 / 1969 / 1805 / 1041 / 903 A |
| Power factor | 0.8 |
Engine, cooling and controls
| Engine model | Volvo Penta TWD1643GE |
|---|---|
| Engine displacement | 984 cu in (16.12 L) |
| Aspiration / cooling | Turbocharged, Charge Air-Cooled |
| Rated engine speed | 1800 rpm |
| Engine oil capacity | 12.7 gal (48.1 L) |
| Engine coolant capacity | 16.4 gal (62 L) |
| Oil capacity | 12.7 gal (48.1 L) |
| Coolant capacity | 43.9 gal (166 L) |
| Maximum ambient | 122 °F (50 °C) |
| Controller | APM402, APM603, Decision-Maker 3000, Decision-Maker 550, Decision-Maker 6000 |
| Alternator | 5M4032 |
| Emissions | Tier 2 |
Physical specifications
| Dry weight | 10, 770 lb (4, 885 kg) |
|---|---|
| Dimensions (L × W × H) | 166.5 × 72 × 78.1 in (4229 × 1829 × 1985 mm) |
Battery
| Battery group | 2 |
|---|---|
| Battery cranking | 925 CCA |
| Battery voltage | 12 V |
| Battery quantity | 2 |
Fuel consumption
| Standby | 11.0 gal/h (41.7 L/h) @ 25%; 20.0 gal/h (75.8 L/h) @ 50%; 29.7 gal/h (112.5 L/h) @ 75%; 40.8 gal/h (154.6 L/h) @ 100% |
|---|---|
| Prime | 10.2 gal/h (38.5 L/h) @ 25%; 18.3 gal/h (69.2 L/h) @ 50%; 26.9 gal/h (101.7 L/h) @ 75%; 36.7 gal/h (139.0 L/h) @ 100% |
Maintenance and service parts
| Engine oil | Capacity: 48.1 L |
|---|---|
| Oil filter | Specification: Cartridge |
| Fuel filter | Part number: 33798; Specification: Primary, 10 Micron/Secondary w/Water Separator, 3 Microns |
| Air filter | Specification: Dry |
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.