Home » Appliances » Kohler 60REOZK Specs (Power | Consumption)

Kohler 60REOZK Specs (Power | Consumption)

The Kohler 60REOZK generator is listed with standby output of 60 kW, Diesel fuel, 60 Hz operation, and 7 available voltage configurations.

Kohler Generator Specifications

Generator • Diesel • 60 Hz

Standby power: 60 kWVoltage options: 7 configurationsDry weight: 1,854 lb (841 kg)

Key specifications

60 kW Standby power
Diesel Fuel
7 configurations Voltage options
1,854 lb (841 kg) Dry weight
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Fuel consumption by load
How fuel use changes as generator load increases.
25% load

1.6 gal/hr

50% load

2.8 gal/hr

75% load

4.3 gal/hr

100% load

5.4 gal/hr

Power-to-weight
Standby output per 1,000 lb of dry weight versus similar-output Kohler models.
This model

32.4 kW

Peer average

29.1 kW

59th percentile
Power output
Low 54 kW High 60 kW
Standby

60 kW

Prime

54 kW

Model spec snapshot
Representative numeric specifications from this generator.
60 kWStandby
1,854.09 lbWeight

How the Kohler 60REOZK compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
60 kW
33% below avg
8th percentile
Dry weight
1,854 lb
51% below avg
1st percentile
Oil capacity
4.12 gal
19% above avg
66th percentile
Standby power60 kW
Low 60 kWAverage 90 kWHigh 127 kW

About 33% below the similar-output Kohler average. Around the 8th percentile for this field.

Dry weight1,854 lb
Low 1,883 lbAverage 3,755 lbHigh 8,555 lb

About 51% below the similar-output Kohler average. Around the 1st percentile for this field.

Oil capacity4.12 gal
Low 1.24 galAverage 3.45 galHigh 7.29 gal

About 19% above the similar-output Kohler average. Around the 66th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model 60REOZK
Generator type Generator
Fuel Diesel
Frequency 60 Hz

Electrical output

Standby power 60 kW
Prime power 54 kW
Standby kVA 75.0
Voltage options 120/208 V, 127/220 V, 120/240 V, 139/240 V, 220/380 V, 277/480 V, 347/600 V
Power factor 0.8

Engine, cooling and controls

Engine model Kohler KDI 3404TM
Engine displacement 207 cu in (3.4 L)
Aspiration / cooling Turbocharged
Rated engine speed 1800 rpm
Engine oil capacity 4.12 gal (15.6 L)
Engine coolant capacity 3.25 gal (12.3 L)
Oil capacity 4.12 gal (15.6 L)
Coolant capacity 3.25 gal (12.3 L)
Maximum ambient 122 °F (50 °C)
Controller APM402, Decision-Maker 3000, Decision-Maker 550
Emissions Tier 3

Physical specifications

Dry weight 1, 854 lb (841 kg)
Dimensions (L × W × H) 90.6 × 40.9 × 44.5 in (2300 × 1040 × 1131 mm)

Battery

Battery cranking 650 CCA
Battery voltage 12 V
Battery quantity 1

Fuel consumption

Standby 1.6 gal/h (6.0 L/h) @ 25%; 2.8 gal/h (10.6 L/h) @ 50%; 4.3 gal/h (16.3 L/h) @ 75%; 5.4 gal/h (20.4 L/h) @ 100%
Prime 1.5 gal/h (5.8 L/h) @ 25%; 2.6 gal/h (9.8 L/h) @ 50%; 3.8 gal/h (14.4 L/h) @ 75%; 4.9 gal/h (18.5 L/h) @ 100%

Maintenance and service parts

Engine oil Interval: 250 hr; Specification: Engine oil level (8); Capacity: 15.6 L
Oil filter Interval: 500 hr; Specification: Engine oil and oil filter cartridge replacement (250, 500); Capacity: ×1
Fuel filter Interval: 1000 hr; Specification: Fuel filter and prefilter cartridge replacement (250, 500)
Air filter Interval: 5000 hr; Specification: Dry
Coolant Interval: 1000 hr; Specification: Coolant level (8) (9), Check coolant level (3.2.2)
Belt Interval: 1500 hr; Specification: Alternator belt (8) (6) (7), Check Poly-V alternator belt (3.2.2)

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.