Home » Appliances » Kohler 60RFZ Specs (Power | Consumption)

Kohler 60RFZ Specs (Power | Consumption)

The Kohler 60RFZ generator is listed with standby output of 50 kW, Gas fuel, 50 Hz operation, 6 available voltage configurations, and Three phase.

Kohler Generator Specifications

Generator • Gas • 50 Hz • Three phase

Standby power: 50 kWVoltage options: 6 configurations

Key specifications

50 kW Standby power
Gas Fuel
6 configurations Voltage options
Three phase Phase
50 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Power output
Low 46 kW High 50 kW
Standby

50 kW

Prime

46 kW

How the Kohler 60RFZ compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
50 kW
22% above avg
82nd percentile
Oil capacity
2.25 gal
11% below avg
44th percentile
Standby power50 kW
Low 30 kWAverage 41.1 kWHigh 55 kW

About 22% above the similar-output Kohler average. Around the 82nd percentile for this field.

Oil capacity2.25 gal
Low 1.09 galAverage 2.52 galHigh 4.12 gal

About 11% below the similar-output Kohler average. Around the 44th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model 60RFZ
Generator type Generator
Fuel Gas
Frequency 50 Hz

Electrical output

Standby power 50 kW
Prime power 46 kW
Standby kVA 63.0
Voltage options 110/220 V, 110/190 V, 220/380 V, 230/400 V, 240/416 V, 120/208 V
Phase Three phase
Power factor 0.8

Engine, cooling and controls

Engine model Ford LSG-875
Engine displacement 460 cu in (7.538 L)
Aspiration / cooling Turbocharger
Rated engine speed 1800 rpm
Engine oil capacity 2.25 gal (8.5 L)
Engine coolant capacity 7.5 gal (28.4 L)
Oil capacity 2.25 gal (8.5 L)
Coolant capacity 6.89 gal (26.1 L)
Maximum ambient 109 °F (43 °C)
Alternator Kohler 4P10 (4-pole, Class H insulation)

Physical specifications

Dimensions (L × W × H) 88.3 × 34 × 44.3 in (2242 × 864 × 1124 mm)

Fuel consumption

Standby 11.9 L/h @ 25%; 17.3 L/h @ 50%; 22.7 L/h @ 75%; 27.2 L/h @ 100%

Maintenance and service parts

Oil filter Interval: 69 hr; Capacity: ×1
Air filter Interval: 69 hr

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.

Ernie Lo