Home » Appliances » Kohler 750REZK Specs (Power | Consumption)

Kohler 750REZK Specs (Power | Consumption)

The Kohler 750REZK generator is listed with standby output of 750 kW, Natural Gas fuel, and 60 Hz operation.

Kohler Generator Specifications

Generator • Natural Gas • 60 Hz

Standby power: 750 kW

Key specifications

750 kW Standby power
Natural Gas Fuel
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Power output
Low 630 kW High 750 kW
Standby

750 kW

Prime

630 kW

How the Kohler 750REZK compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
750 kW
21% above avg
70th percentile
Oil capacity
45.97 gal
120% above avg
95th percentile
Standby power750 kW
Low 400 kWAverage 620.7 kWHigh 931 kW

About 21% above the similar-output Kohler average. Around the 70th percentile for this field.

Oil capacity45.97 gal
Low 9.3 galAverage 20.9 galHigh 48.71 gal

About 120% above the similar-output Kohler average. Around the 95th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model 750REZK
Generator type Generator
Fuel Natural Gas
Frequency 60 Hz

Electrical output

Standby power 750 kW
Prime power 630 kW
Standby kVA 937.0

Engine, cooling and controls

Engine model Dresser-Rand SFGLD360
Engine displacement 2, 191 cu in (35.9 L)
Aspiration / cooling Turbocharged, Charge Air-Cooled
Rated engine speed 1800 rpm
Engine oil capacity 46 gal (174 L)
Engine coolant capacity 59.4 gal (225 L)
Oil capacity 46 gal (174 L)
Controller Decision-Maker 8000
Alternator 5M4036
Emissions EPA-Certified for Stationary Emergency and Non-Emergency Applications

Fuel consumption

Standby 69.0 L/h @ 25%; 116.0 L/h @ 50%; 164.0 L/h @ 75%; 212.0 L/h @ 100%
Prime 63.0 L/h @ 25%; 105.0 L/h @ 50%; 147.0 L/h @ 75%; 189.0 L/h @ 100%

Maintenance and service parts

Oil filter Capacity: ×3

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.