The Kohler 750REZK generator is listed with standby output of 750 kW, Natural Gas fuel, and 60 Hz operation.
Generator • Natural Gas • 60 Hz
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
750 kW
630 kW
How the Kohler 750REZK compares
This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.
About 21% above the similar-output Kohler average. Around the 70th percentile for this field.
About 120% above the similar-output Kohler average. Around the 95th percentile for this field.
Generator information
| Manufacturer | Kohler |
|---|---|
| Model | 750REZK |
| Generator type | Generator |
| Fuel | Natural Gas |
| Frequency | 60 Hz |
Electrical output
| Standby power | 750 kW |
|---|---|
| Prime power | 630 kW |
| Standby kVA | 937.0 |
Engine, cooling and controls
| Engine model | Dresser-Rand SFGLD360 |
|---|---|
| Engine displacement | 2, 191 cu in (35.9 L) |
| Aspiration / cooling | Turbocharged, Charge Air-Cooled |
| Rated engine speed | 1800 rpm |
| Engine oil capacity | 46 gal (174 L) |
| Engine coolant capacity | 59.4 gal (225 L) |
| Oil capacity | 46 gal (174 L) |
| Controller | Decision-Maker 8000 |
| Alternator | 5M4036 |
| Emissions | EPA-Certified for Stationary Emergency and Non-Emergency Applications |
Fuel consumption
| Standby | 69.0 L/h @ 25%; 116.0 L/h @ 50%; 164.0 L/h @ 75%; 212.0 L/h @ 100% |
|---|---|
| Prime | 63.0 L/h @ 25%; 105.0 L/h @ 50%; 147.0 L/h @ 75%; 189.0 L/h @ 100% |
Maintenance and service parts
| Oil filter | Capacity: ×3 |
|---|
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.