Home » Appliances » Kohler 800REOZMD Specs (Power | Consumption)

Kohler 800REOZMD Specs (Power | Consumption)

The Kohler 800REOZMD generator is listed with standby output of 810 kW, Diesel fuel, 60 Hz operation, 4 available voltage configurations, and Three phase.

Kohler Generator Specifications

Generator • Diesel • 60 Hz • Three phase

Standby power: 810 kWVoltage options: 4 configurations

Key specifications

810 kW Standby power
Diesel Fuel
4 configurations Voltage options
Three phase Phase
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Fuel consumption by load
How fuel use changes as generator load increases.
25% load

17.6 gal/hr

50% load

31.3 gal/hr

75% load

46.1 gal/hr

100% load

67.4 gal/hr

Power output
Low 730 kW High 810 kW
Standby

810 kW

Prime

730 kW

How the Kohler 800REOZMD compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
810 kW
30% above avg
83rd percentile
Oil capacity
31.7 gal
52% above avg
85th percentile
Standby power810 kW
Low 400 kWAverage 620.7 kWHigh 931 kW

About 30% above the similar-output Kohler average. Around the 83rd percentile for this field.

Oil capacity31.7 gal
Low 9.3 galAverage 20.9 galHigh 48.71 gal

About 52% above the similar-output Kohler average. Around the 85th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model 800REOZMD
Generator type Generator
Fuel Diesel
Frequency 60 Hz

Electrical output

Standby power 810 kW
Prime power 730 kW
Standby kVA 1013.0
Voltage options 240/416 V, 277/480 V, 220/380 V, 347/600 V
Phase Three phase
Power factor 0.8

Engine, cooling and controls

Engine model Mitsubishi S12A2-Y2PTAW-2
Engine displacement 2, 071 cu in (33.93 L)
Aspiration / cooling Turbocharged
Rated engine speed 1800 rpm
Engine oil capacity 31.7 gal (120 L)
Engine coolant capacity 80 gal (303 L)
Oil capacity 31.7 gal (120 L)
Coolant capacity 80 gal (303 L)
Maximum ambient 122 °F (50 °C)
Alternator 5M4034
Emissions Tier 2 EPA-Certified for Stationary Emergency Applications

Physical specifications

Dimensions (L × W × H) 195.6 × 73 × 95.2 in (4968 × 1854 × 2419 mm)

Battery

Battery cranking 1150 CCA
Battery voltage 12 V
Battery quantity 2

Fuel consumption

Standby 17.6 gal/h (66.7 L/h) @ 25%; 31.3 gal/h (118.6 L/h) @ 50%; 46.1 gal/h (174.4 L/h) @ 75%; 67.4 gal/h (255.1 L/h) @ 100%
Prime 16.7 gal/h (63.0 L/h) @ 25%; 28.6 gal/h (108.4 L/h) @ 50%; 41.9 gal/h (158.8 L/h) @ 75%; 58.7 gal/h (222.1 L/h) @ 100%

Maintenance and service parts

Engine oil Specification: Class CD or CF oil (API service classification); Capacity: 120.0 L
Oil filter Part number: GM32057; Capacity: ×3
Fuel filter Part number: — | GM13951; Specification: Secondary; Capacity: ×3
Air filter Specification: Dry, Replaceable Cartridge
Coolant Capacity: 303.0 L

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.