Home » Appliances » Kohler GMKD1350 Specs (Power | Consumption)

Kohler GMKD1350 Specs (Power | Consumption)

The Kohler GMKD1350 generator is listed with standby output of 1200 kW, Diesel fuel, 50 Hz operation, 4 available voltage configurations, and Three phase.

Kohler Generator Specifications

Generator • Diesel • 50 Hz • Three phase

Standby power: 1200 kWVoltage options: 4 configurations

Key specifications

1200 kW Standby power
Diesel Fuel
4 configurations Voltage options
Three phase Phase
50 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Fuel consumption by load
How fuel use changes as generator load increases.
25% load

22.2 gal/hr

50% load

42 gal/hr

75% load

61.8 gal/hr

100% load

83.5 gal/hr

Estimated runtime by load
Calculated from the listed 1,548.8 gal fuel capacity and fuel-consumption data.
25% load

69.8 hr

50% load

36.9 hr

75% load

25.1 hr

100% load

18.5 hr

Power output
Low 1,080 kW High 1,200 kW
Standby

1,200 kW

Prime

1,080 kW

How the Kohler GMKD1350 compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
1,200 kW
38% below avg
15th percentile
Oil capacity
35.66 gal
46% below avg
10th percentile
Standby power1,200 kW
Low 1,000 kWAverage 1,949.6 kWHigh 3,480 kW

About 38% below the similar-output Kohler average. Around the 15th percentile for this field.

Oil capacity35.66 gal
Low 25.87 galAverage 65.49 galHigh 110.95 gal

About 46% below the similar-output Kohler average. Around the 10th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model GMKD1350
Generator type Generator
Fuel Diesel
Frequency 50 Hz

Electrical output

Standby power 1200 kW
Prime power 1080 kW
Standby kVA 1500.0
Voltage options 220/380 V, 230/400 V, 240/415 V, 1905/3300 V
Phase Three phase
Power factor 0.8

Engine, cooling and controls

Engine model Kohler KD36V16
Engine displacement 2, 197 cu in (36 L)
Aspiration / cooling Turbocharged, Intercooled
Rated engine speed 1500 rpm
Engine oil capacity 35.7 gal (135 L)
Engine coolant capacity 62.1 gal (235 L)
Oil capacity 35.7 gal (135 L)
Coolant capacity 62.1 gal (235 L)
Maximum ambient 104 °F (40 °C)
Controller APM603, APM802
Alternator KH03850TO4D

Physical specifications

Dimensions (L × W × H) 208.3 × 86 × 91 in (5291 × 2184 × 2311 mm)

Battery

Battery cranking 1110 CCA
Battery voltage 12 V
Battery quantity 4

Fuel system and runtime

Fuel tank 1, 548.8 gal (5, 863 L)

Fuel consumption

Standby 22.2 gal/h (84.0 L/h) @ 25%; 42.0 gal/h (159.0 L/h) @ 50%; 61.8 gal/h (234.0 L/h) @ 75%; 83.5 gal/h (316.0 L/h) @ 100%
Prime 20.6 gal/h (78.0 L/h) @ 25%; 38.3 gal/h (145.0 L/h) @ 50%; 56.3 gal/h (213.0 L/h) @ 75%; 75.8 gal/h (287.0 L/h) @ 100%

Maintenance and service parts

Engine oil Interval: 1000 hr; Specification: Lubricant Category 3 (Standard); Capacity: 150.0 l
Oil filter Interval: 1000 hr; Specification: With Category 3 oil (Standard); Capacity: ×4
Fuel filter Interval: 1000 hr; Specification: Primary fuel filter; Capacity: ×1
Air filter Interval: 3000 hr; Specification: Air filter main element
Coolant Interval: 8000 hr; Specification: BASF GLYSANTIN G40 (With analysis extension); Capacity: 124.0 l
Belt Interval: 4000 hr; Specification: V-ribbed belt for battery charging alternator (PRP / COP)

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.