The Kohler GMKD2000 generator is listed with standby output of 2000 kW, Diesel fuel, 60 Hz operation, 9 available voltage configurations, and Three phase.
Generator • Diesel • 60 Hz • Three phase
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
49.1 gal/hr
81.3 gal/hr
114.3 gal/hr
149.1 gal/hr
46.1 hr
27.9 hr
19.8 hr
15.2 hr
2,000 kW
1,810 kW
How the Kohler GMKD2000 compares
This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.
Very close to the similar-output Kohler average. Around the 56th percentile for this field.
About 35% above the similar-output Kohler average. Around the 78th percentile for this field.
Generator information
| Manufacturer | Kohler |
|---|---|
| Model | GMKD2000 |
| Generator type | Generator |
| Fuel | Diesel |
| Frequency | 60 Hz |
Electrical output
| Standby power | 2000 kW |
|---|---|
| Prime power | 1810 kW |
| Standby kVA | 2500.0 |
| Voltage options | 220/380 V, 240/416 V, 277/480 V, 347/600 V, 2400/4160 V, 3810/6600 V, 7200/1247 V, 7620/1320 V, 7970/1380 V |
| Phase | Three phase |
| Power factor | 0.8 |
Engine, cooling and controls
| Engine model | Kohler KD62V12 |
|---|---|
| Engine displacement | 3, 783 cu in (62 L) |
| Aspiration / cooling | Turbocharged, Intercooled |
| Rated engine speed | 1800 rpm |
| Engine oil capacity | 88.5 gal (335 L) |
| Engine coolant capacity | 94 gal (356 L) |
| Oil capacity | 88.5 gal (335 L) |
| Coolant capacity | 169.9 gal (643 L) |
| Maximum ambient | 122 °F (50 °C) |
| Controller | APM603, APM802 |
| Alternator | KH07770TO4D, KH08430TO4D, KH06220TO4D, KH07000TO4D, KH07080TO4D, KH07630TO4D, KH09270TO4D |
| Emissions | Tier 2 |
Physical specifications
| Dimensions (L × W × H) | 273.9 × 114.8 × 130 in (6958 × 2915 × 3301 mm) |
|---|
Battery
| Battery cranking | 1110 CCA |
|---|---|
| Battery voltage | 12 V |
| Battery quantity | 4 |
Fuel system and runtime
| Fuel tank | 2, 265.8 gal (8, 577 L) |
|---|
Fuel consumption
| Standby | 49.1 gal/h (186.0 L/h) @ 25%; 81.3 gal/h (308.0 L/h) @ 50%; 114.3 gal/h (433.0 L/h) @ 75%; 149.1 gal/h (564.0 L/h) @ 100% |
|---|---|
| Prime | 45.5 gal/h (172.0 L/h) @ 25%; 75.8 gal/h (287.0 L/h) @ 50%; 106.0 gal/h (401.0 L/h) @ 75%; 136.3 gal/h (516.0 L/h) @ 100% |
Maintenance and service parts
| Oil filter | Part number: 230510002 |
|---|---|
| Fuel filter | Part number: 230510004 |
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.