The Kohler GMKD3250 generator is listed with standby output of 3250 kW, #2 Diesel ULSD / HVO / RD fuel, 60 Hz operation, 7 available voltage configurations, Three phase, and sound level of 99 dBA @ 23 ft (7 m).

Kohler Generator Specifications

Generator • #2 Diesel ULSD / HVO / RD • 60 Hz • Three phase

Standby power: 3250 kWVoltage options: 7 configurations

Key specifications

3250 kW Standby power
#2 Diesel ULSD / HVO / RD Fuel
7 configurations Voltage options
Three phase Phase
99 dBA @ 23 ft (7 m) Sound level
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Fuel consumption by load
How fuel use changes as generator load increases.
25% load

73.5 gal/hr

50% load

127.4 gal/hr

75% load

191.9 gal/hr

100% load

216.6 gal/hr

Power output
Low 2,950 kW High 3,250 kW
Standby

3,250 kW

Prime

2,950 kW

Model spec snapshot
Representative numeric specifications from this generator.
3,250 kWStandby
99 dBASound

How the Kohler GMKD3250 compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
3,250 kW
67% above avg
94th percentile
Sound level
99 dBA
In line with avg
83rd percentile
Oil capacity
110.95 gal
69% above avg
94th percentile
Standby power3,250 kW
Low 1,000 kWAverage 1,949.6 kWHigh 3,480 kW

About 67% above the similar-output Kohler average. Around the 94th percentile for this field.

Sound level99 dBA
Low 87.2 dBAAverage 96.5 dBAHigh 99 dBA

Very close to the similar-output Kohler average. Around the 83rd percentile for this field.

Oil capacity110.95 gal
Low 25.87 galAverage 65.49 galHigh 110.95 gal

About 69% above the similar-output Kohler average. Around the 94th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model GMKD3250
Generator type Generator
Fuel #2 Diesel ULSD / HVO / RD
Frequency 60 Hz

Electrical output

Standby power 3250 kW
Prime power 2950 kW
Standby kVA 4062.0
Voltage options 2400/4160 V, 3810/6600 V, 7200/1247 V, 7620/1320 V, 7970/1380 V, 277/480 V, 347/600 V
Phase Three phase
Power factor 0.8

Engine, cooling and controls

Engine model Kohler KD83V16
Engine displacement 5, 065 cu in (83 L)
Aspiration / cooling Turbocharged, Intercooled
Rated engine speed 1800 rpm
Engine oil capacity 111 gal (420 L)
Engine coolant capacity 99.1 gal (375 L)
Oil capacity 111 gal (420 L)
Coolant capacity 314.9 gal (1, 192 L)
Maximum ambient 122 °F (50 °C)
Controller APM603, APM802
Alternator KH07631TO4D, KH07632TO4D, KH07640TO4D, KH08590TO4D, KH09390TO4D, KH09370TO4D
Emissions Tier 2

Physical specifications

Dimensions (L × W × H) 301.2 × 124.9 × 135.9 in (7650 × 3172 × 3451 mm)
Sound level 99 dBA @ 23 ft (7 m)

Battery

Battery cranking 1110 CCA
Battery voltage 12 V
Battery quantity 4

Fuel consumption

Standby 73.5 gal/h (278.0 L/h) @ 25%; 127.4 gal/h (482.0 L/h) @ 50%; 191.9 gal/h (726.0 L/h) @ 75%; 216.6 gal/h (820.0 L/h) @ 100%
Prime 64.1 gal/h (243.0 L/h) @ 25%; 123.2 gal/h (466.0 L/h) @ 50%; 169.7 gal/h (642.0 L/h) @ 75%; 203.7 gal/h (771.0 L/h) @ 100%

Maintenance and service parts

Oil filter Part number: 230510002; Capacity: ×8
Fuel filter Part number: — | 330510016; Specification: Primary Engine Filter; Capacity: ×3

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.