Home » Appliances » Kohler GMKD3500 Specs (Power | Consumption)

Kohler GMKD3500 Specs (Power | Consumption)

The Kohler GMKD3500 generator is listed with standby output of 3500 kW, Diesel fuel, 60 Hz operation, 7 available voltage configurations, Three phase, and sound level of 99 dBA @ 23 ft (7 m).

Kohler Generator Specifications

Generator • Diesel • 60 Hz • Three phase

Standby power: 3500 kWVoltage options: 7 configurations

Key specifications

3500 kW Standby power
Diesel Fuel
7 configurations Voltage options
Three phase Phase
99 dBA @ 23 ft (7 m) Sound level
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Fuel consumption by load
How fuel use changes as generator load increases.
25% load

78 gal/hr

50% load

137.2 gal/hr

75% load

198.8 gal/hr

100% load

241.8 gal/hr

Power output
Low 3,180 kW High 3,500 kW
Standby

3,500 kW

Prime

3,180 kW

Model spec snapshot
Representative numeric specifications from this generator.
3,500 kWStandby
99 dBASound

How the Kohler GMKD3500 compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
3,500 kW
80% above avg
97th percentile
Sound level
99 dBA
In line with avg
83rd percentile
Oil capacity
184.92 gal
182% above avg
99th percentile
Standby power3,500 kW
Low 1,000 kWAverage 1,949.6 kWHigh 3,480 kW

About 80% above the similar-output Kohler average. Around the 97th percentile for this field.

Sound level99 dBA
Low 87.2 dBAAverage 96.5 dBAHigh 99 dBA

Very close to the similar-output Kohler average. Around the 83rd percentile for this field.

Oil capacity184.92 gal
Low 25.87 galAverage 65.49 galHigh 110.95 gal

About 182% above the similar-output Kohler average. Around the 99th percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model GMKD3500
Generator type Generator
Fuel Diesel
Frequency 60 Hz

Electrical output

Standby power 3500 kW
Prime power 3180 kW
Standby kVA 4375.0
Voltage options 2400/4160 V, 3810/6600 V, 7200/1247 V, 7620/1320 V, 7970/1380 V, 277/480 V, 347/600 V
Phase Three phase
Power factor 0.8

Engine, cooling and controls

Engine model Kohler KD103V20
Engine displacement 6, 285 cu in (103 L)
Aspiration / cooling Turbocharged, Intercooled
Rated engine speed 1800 rpm
Engine oil capacity 184.9 gal (700 L)
Engine coolant capacity 105.7 gal (400 L)
Oil capacity 184.9 gal (700 L)
Coolant capacity 321.5 gal (1, 217 L)
Maximum ambient 122 °F (50 °C)
Controller APM603, APM802
Alternator KH07632TO4D, KH09370TO4D, KH10171TO4D, KH08590TO4D, KH09390TO4D (4-pole, Class H insulation)
Emissions Tier 2

Physical specifications

Dimensions (L × W × H) 325.3 × 124.9 × 135.9 in (8263 × 3172 × 3451 mm)
Sound level 99 dBA @ 23 ft (7 m)

Battery

Battery cranking 1110 CCA
Battery voltage 12 V
Battery quantity 4

Fuel consumption

Standby 78.0 gal/h (295.0 L/h) @ 25%; 137.2 gal/h (519.0 L/h) @ 50%; 198.8 gal/h (753.0 L/h) @ 75%; 241.8 gal/h (915.0 L/h) @ 100%
Prime 72.5 gal/h (274.0 L/h) @ 25%; 125.8 gal/h (476.0 L/h) @ 50%; 178.4 gal/h (675.0 L/h) @ 75%; 219.8 gal/h (832.0 L/h) @ 100%

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.