The Kohler KD1500 generator is listed with standby output of 1500 kW, Diesel fuel, 50 Hz operation, 600 V output, and Three phase.
Generator • Diesel • 50 Hz • Three phase
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
31.43 gal/hr
55.75 gal/hr
80.01 gal/hr
103.74 gal/hr
49.3 hr
27.8 hr
19.4 hr
14.9 hr
52.8 kW
51.6 kW
1,500 kW
1,150 kW
How the Kohler KD1500 compares
This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.
About 23% below the similar-output Kohler average. Around the 33rd percentile for this field.
About 16% below the similar-output Kohler average. Around the 37th percentile for this field.
About 46% below the similar-output Kohler average. Around the 10th percentile for this field.
Generator information
| Manufacturer | Kohler |
|---|---|
| Model | KD1500 |
| Generator type | Generator |
| Fuel | Diesel |
| Frequency | 50 Hz |
Electrical output
| Standby power | 1500 kW |
|---|---|
| Prime power | 1150 kW |
| Standby kVA | 1625.0 |
| Voltage options | 600 V |
| Phase | Three phase |
| Power factor | 0.8 |
Engine, cooling and controls
| Engine model | Kohler KD36V16 |
|---|---|
| Engine displacement | 2, 197 cu in (36 L) |
| Aspiration / cooling | Turbocharged, Intercooled |
| Rated engine speed | 1500 rpm |
| Engine oil capacity | 35.7 gal (135 L) |
| Engine coolant capacity | 62.1 gal (235 L) |
| Oil capacity | 35.7 gal (135 L) |
| Coolant capacity | 143 / 287 L |
| Maximum ambient | 122 °F (50 °C) |
| Controller | APM802 |
| Emissions | Tier 2 |
Physical specifications
| Dry weight | 28, 431 lb (12, 896 kg) |
|---|---|
| Dimensions (L × W × H) | 222 × 86 × 98 in (5639 × 2184 × 2489 mm) |
Fuel system and runtime
| Fuel tank | 1, 548.8 gal (5, 863 L) |
|---|
Maintenance and service parts
| Engine oil | Interval: 1000 hr; Specification: Lubricant Category 3 (Standard); Capacity: 150.0 l |
|---|---|
| Oil filter | Interval: 1000 hr; Specification: With Category 3 oil (Standard); Capacity: ×4 |
| Fuel filter | Interval: 1000 hr; Specification: Primary fuel filter; Capacity: ×1 |
| Air filter | Interval: 3000 hr; Specification: Air filter main element |
| Coolant | Interval: 8000 hr; Specification: BASF GLYSANTIN G40 (With analysis extension); Capacity: 124.0 l |
| Belt | Interval: 4000 hr; Specification: V-ribbed belt for battery charging alternator (PRP / COP) |
Estimated fuel consumption
| 25% load | 31.43 gal/hr (119 L/hr) |
|---|---|
| 50% load | 55.75 gal/hr (211 L/hr) |
| 75% load | 80.01 gal/hr (302.9 L/hr) |
| 100% load | 103.74 gal/hr (392.7 L/hr) |
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.