The Kohler KDI 2504 TCR generator is listed with standby output of 39 kW, Diesel fuel, and 50 Hz operation.
Generator • Diesel • 50 Hz
Key specifications
Useful generator charts
Charts are shown only when this model has enough usable source data.
1.1 gal/hr
1.92 gal/hr
2.74 gal/hr
3.58 gal/hr
66.3 kW
24.9 kW
39 kW
35 kW
How the Kohler KDI 2504 TCR compares
This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.
About 5% below the similar-output Kohler average. Around the 41st percentile for this field.
About 70% below the similar-output Kohler average. Around the 1st percentile for this field.
About 21% above the similar-output Kohler average. Around the 70th percentile for this field.
Generator information
| Manufacturer | Kohler |
|---|---|
| Model | KDI 2504 TCR |
| Generator type | Generator |
| Fuel | Diesel |
| Frequency | 50 Hz |
Electrical output
| Standby power | 39 kW |
|---|---|
| Prime power | 35 kW |
| Standby kVA | 49.0 |
Engine, cooling and controls
| Engine model | Kohler KDI 2504 TCR |
|---|---|
| Engine displacement | 153 cu in (2.5 L) |
| Aspiration / cooling | Turbocharged |
| Rated engine speed | 1800 rpm |
| Engine oil capacity | 2.96 gal (11.2 L) |
| Engine coolant capacity | 4.54 gal (17.2 L) |
| Oil capacity | 3.04 gal (11.5 L) |
| Emissions | EU STAGE V |
Physical specifications
| Dry weight | 589 lb (267 kg) |
|---|
Maintenance and service parts
| Engine oil | Part number: ED0053029490; Interval: 600 hr; Specification: Place engine on level surface to ensure accurate measurement of oil level.; Capacity: 8.9 l |
|---|---|
| Oil filter | Interval: 600 hr; Specification: Remove the oil dipstick B. Remove the oil drain plug D and the gasket E (the oil drain plug is on both sides of the oil sump). Drain oil in an appropriate container. |
| Fuel filter | Interval: 600 hr; Specification: Replace the fuel filter |
| Air filter | Interval: 1000 hr; Specification: Replace with a new filter |
| Coolant | Interval: 5000 hr; Specification: Top liquid up until the pipes inside the radiator are covered by about 5 mm. Do not overfill the radiator, but leave room for the coolant to expand. |
| Belt | Interval: 1500 hr; Specification: Check by the appropriate tool that at point p the tension value is between 80 and 85 Hz. Using the tool F (DENSO BTG-2 or a similar one) shown in the picture, it is possible to check the corresponding value in Newtons, which should be between 350 and 450 N. |
Estimated fuel consumption
| 25% load | 1.1 gal/hr (4.2 L/hr) |
|---|---|
| 50% load | 1.92 gal/hr (7.3 L/hr) |
| 75% load | 2.74 gal/hr (10.4 L/hr) |
| 100% load | 3.58 gal/hr (13.6 L/hr) |
Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.