Home » Appliances » Kohler KG125 Specs (Power | Consumption)

Kohler KG125 Specs (Power | Consumption)

The Kohler KG125 generator is listed with standby output of 125 kW, L.P./N.G. fuel, 60 Hz operation, 7 available voltage configurations, Three phase, and rated current of 417 A.

Kohler Generator Specifications

Generator • L.P./N.G. • 60 Hz • Three phase

Standby power: 125 kWVoltage options: 7 configurationsRated current: 417 A

Key specifications

125 kW Standby power
L.P./N.G. Fuel
7 configurations Voltage options
Three phase Phase
417 A Rated current
60 Hz Frequency

Useful generator charts

Charts are shown only when this model has enough usable source data.

Model spec snapshot
Representative numeric specifications from this generator.
125 kWStandby
417 ACurrent

How the Kohler KG125 compares

This compares the supplied numeric specification with Kohler generators in the same broad standby-power class where enough comparable data exists.

Standby power
125 kW
39% above avg
91st percentile
Rated current
417 A
55% above avg
90th percentile
Oil capacity
2.38 gal
31% below avg
41st percentile
Standby power125 kW
Low 60 kWAverage 90 kWHigh 127 kW

About 39% above the similar-output Kohler average. Around the 91st percentile for this field.

Rated current417 A
Low 106 AAverage 269 AHigh 454 A

About 55% above the similar-output Kohler average. Around the 90th percentile for this field.

Oil capacity2.38 gal
Low 1.24 galAverage 3.45 galHigh 7.29 gal

About 31% below the similar-output Kohler average. Around the 41st percentile for this field.

This model Peer average

Generator information

Manufacturer Kohler
Model KG125
Generator type Generator
Fuel L.P./N.G.
Frequency 60 Hz

Electrical output

Standby power 125 kW
Standby kVA 150.0
Voltage options 120/208 V, 127/220 V, 120/240 V, 139/240 V, 220/380 V, 277/480 V, 347/600 V
Phase Three phase
Rated current 417 A
Power factor 0.8

Engine, cooling and controls

Engine model Kohler KG6208THD
Engine displacement 378 cu in (6.2 L)
Aspiration / cooling Turbocharged, Aftercooled
Rated engine speed 1800 rpm
Engine oil capacity 2.38 gal (9 L)
Engine coolant capacity 7.5 gal (28.4 L)
Oil capacity 2.38 gal (9 L)
Coolant capacity 7.5 gal (28.4 L)
Maximum ambient 122 °F (50 °C)
Controller APM402
Alternator Kohler 4R12X
Emissions EPA-Certified for 60 Hz Stationary Emergency Applications

Physical specifications

Dimensions (L × W × H) 110.2 × 44.1 × 60.2 in (2800 × 1120 × 1528 mm)

Battery

Battery cranking 650 CCA
Battery voltage 12 V
Battery quantity 1

Fuel consumption

Standby 25%; 50%; 75%; 100%

Maintenance and service parts

Engine oil Capacity: 9.0 L
Oil filter Specification: Cartridge; Capacity: ×1

Disclaimer: Specifications should be verified against the official owner’s or service manual and confirmed on the Kohler North America generator website.